Skip to content

Product Recall Number: 14-713

Why was System Sensor reflected beam smoke detectors recalled?

When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

System Sensor reflected beam smoke detectors
Here's product recall specific data for System Sensor reflected beam smoke detectors.

  • Product Recall Number: 14-713

  • Product Safety Warning Number:

  • Date: 2014-01-28

  • Product Safety Warning Date:

  • Name Of Product: System Sensor reflected beam smoke detectors

  • Description: This recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7? inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.

  • Hazard Description: When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

  • Consumer Action: None Listed

  • Original Product Safety Warning Announcement: None Listed

  • Remedy Type: Replace

  • Units: About 610

  • Incidents: None reported

  • Remedy: Owners with the affected smoke detectors powered by a power supply that is not on the company's acceptable list available online, should contact System Sensor to receive free replacement smoke detectors. System Sensor and its distributors are contacting purchasers directly.

  • Sold At: Alarm system, security equipment and electrical equipment contractors and dealers for use in commercial building fire alarm systems from November 2012 through May 2013 for about $800. 

  • Importers: None Listed

  • Manufacturers: None Listed

  • Distributors: None Listed

  • Manufactured In: United States

  • Custom Label: None Listed

  • Custom Field: None Listed