Skip to content

Product Recall Number: 03-003

Why was Siebe actuators recalled?

A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Siebe actuators
Here's product recall specific data for Siebe actuators.

  • Product Recall Number: 03-003

  • Product Safety Warning Number:

  • Date: 2002-10-01

  • Product Safety Warning Date:

  • Name Of Product: Siebe actuators

  • Description: WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Invensys Building Systems, of Love Park, Ill., is recalling up to 560,000 Siebe actuators for testing and replacement, if necessary, which could be found in fire and smoke dampers. Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing. These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.

  • Hazard Description: A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

  • Consumer Action: None Listed

  • Original Product Safety Warning Announcement: None Listed

  • Remedy Type: Replace

  • Units: Up to 560,000

  • Incidents: Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.

  • Remedy: To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.

  • Sold At: None Listed

  • Importers: None Listed

  • Manufacturers: None Listed

  • Distributors: None Listed

  • Manufactured In: None Listed

  • Custom Label: None Listed

  • Custom Field: None Listed