Why was SR-RN-2 and SR-RN2R Boiler Control recalled?

The controls have an electronic relay that may fail in a manner that will allow the burner to operate and by-pass the interlock with the flue damper. The interlock assures proper operation of the damper for removal of combustion gases. If the interlock fails, excess carbon monoxide emissions may occur.

SR-RN-2 and SR-RN2R Boiler Control
Here's product recall specific data for SR-RN-2 and SR-RN2R Boiler Control.

  • Product Recall Number: 02-524

  • Product Safety Warning Number:

  • Date: 2002-03-12

  • Product Safety Warning Date:

  • Name Of Product: SR-RN-2 and SR-RN2R Boiler Control

  • Description: Viessmann Manufacturing Company (U.S.) of Warwick, R.I. is recalling 190 SR-RN2 or SR-RN2R controls, which are installed in Atola-RN Boilers. The recalled units were manufactured between December 1998 and December 2001. This is the entire production of these controls. (The controls do not have a date code that can be seen by consumers.)

  • Hazard Description: The controls have an electronic relay that may fail in a manner that will allow the burner to operate and by-pass the interlock with the flue damper. The interlock assures proper operation of the damper for removal of combustion gases. If the interlock fails, excess carbon monoxide emissions may occur.

  • Consumer Action: None Listed

  • Original Product Safety Warning Announcement: None Listed

  • Remedy Type: Repair

  • Units: None Listed

  • Incidents: No injuries have been reported.

  • Remedy: Consumers who have one of these boilers should contact their local distributor or Ms. Ulli Hiltz, the Viessmann Manufacturing Company contact. Viessmann Manufacturing Company will install a wiring module in suspect boilers which will put a redundant switch in series with the switch that may erroneously close and by-pass the safety interlock with flue damper.Viessmann Manufacturing Company has contacted distributors and wholesalers and made arrangements for them to contact customers and make arrangements to retrofit the Atola-RN Boilers with SR-RN2 or SR-RN2R Controls.

  • Sold At: The boilers were sold nationwide by wholesalers and distributors.

  • Importers: None Listed

  • Manufacturers: None Listed

  • Distributors: None Listed

  • Manufactured In: None Listed

  • Custom Label: None Listed

  • Custom Field: None Listed